Módulo de expansión de 3 Entradas Analógias 4 Pt100 2 Salidas Analógicas
Expansions Modules HV-E3AI4PT1002AO
3 channels of 14 bits precision current input, 4 channels of PT100 temperature input and 2 channels 10 bits precision voltage output.
3 channels of current,0~20mA and 4~20mA are optional; 2 channels of voltage, 0~5V and 0~10V are optional. They can be set by host machine.
Platinum resistance input, PT100.
3 channels A/D and 4 channels PT input with PID adjust function.
Can be set as special function module for HV series PLC, up to 7 modules can be connected.
PRODUCTS STANDARS
1. General Specifications.
| 
 Item  | 
 Analog current input(AD)  | 
 Temperature input (PT)  | 
 Analog voltage output(DA)  | 
| 
 Analog input  | 
 DC0~20mA、4~20mA  | 
 PT100  | 
 -  | 
| 
 Range of temperature detect  | 
 -  | 
 -100~350℃  | 
 -  | 
| 
 Max output range  | 
 DC0~40mA  | 
 -  | 
 -  | 
| 
 Range of analog output  | 
 -  | 
 -  | 
 DC0~5V、0~10V (External load resistance 2KΩ~1MΩ)  | 
| 
 Range of digital input  | 
 -  | 
 -  | 
 10 bits(0~1023)  | 
| 
 Range of digital output  | 
 14 bits(0~16383)  | 
 -1000~3500  | 
 -  | 
| 
 Resolution  | 
 1/16383(14Bit); Converted data are stored in PLC(14Bit) in hex form  | 
 0.1℃  | 
 1/1023(10Bit); Converted data are stored in PLC in hex form(10Bit)  | 
| 
 PID output value  | 
 0~K4095  | 
 -  | 
|
| 
 Integrated accuracy  | 
 0.8%  | 
 ±0.5℃  | 
 0.8%  | 
| 
 Convert speed  | 
 20ms/1 channel  | 
 3ms/1 channel  | 
|
| 
 Power for analog  | 
 DC24V±10%,100mA  | 
||
| 
 Installation  | 
 Fixed with M3 strews or directly installed in DIN46277(35mm width) guide rail  | 
||
| 
 External dimension  | 
 63mm×102mm×73.3mm  | 
||